Commissioning
5.3 Commissioning using a BOP-2 operator panel
Procedure when using the BOP-2 operator panel
To start the motor data identification, proceed as follows:
1.
2.
3.
4.
5.
6.
You have now completed motor data identification.
106
Press the HAND/AUTO key. The BOP-2 displays the symbol for man-
ual operation.
Switch on the motor.
The motor data identification takes several seconds.
Wait until the inverter switches off the motor after motor data identifi-
cation has been completed.
If you have also selected a rotating measurement in addition to the
motor data identification, then the inverter again issues the alarm
A07991.
Switch the motor on again in order to optimize the rotating measure-
ment.
Wait until the inverter switches off the motor after completion of the
optimization. The optimization time depends on the rated motor pow-
er: 20 s ... 2 min.
Switch the inverter control from HAND to AUTO.
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC