Advanced commissioning
6.4 Setpoint calculation
6.4.4
Skip frequency bands and minimum speed
Skip frequency bands
The converter has four skip frequency bands that prevent continuous motor operation within
a specific speed range. You can find additional information in function diagram 3050 of the
List Manual, see also: Manuals for your inverter (Page 409).
Minimum speed
The converter prevents continuous motor operation at speeds < minimum speed.
Speeds where the absolute value is less than the minimum speed are only possible during
motor operation when accelerating or braking.
Table 6- 27
Parameter
p1080
p1106
186
Setting the minimum speed
Description
Minimum speed (factory setting: 0 rpm)
CI: Minimum speed signal source (factory setting: 0)
Dynamic specification of the minimum speed
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
SINAMICS G120C converter