Advanced commissioning
6.2 Inverter control
6.2.2.5
Analog output
Overview
Define the analog output type
The inverter offers a series of default settings, which you can select using parameter
p0776[0]:
Current output (factory setting)
Voltage output
Current output
Characteristics
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 6-4
140
Examples for scaling characteristics
Changing the function of the analog output:
1. Define the analog output type using parameter
p0776[0].
2. Interconnect parameter p0771 with a connector
output of your choice.
See also Section: Interconnecting signals in the
converter (Page 399).
Connector outputs are marked with "CO" in the
parameter list of the List Manual.
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
p0776[0] =
0
1
2
SINAMICS G120C converter