Advanced commissioning
6.7 Application-specific functions
6.7.9.3

Optimizing the controller

Setting the technology controller without autotuning (manual)
Procedure
Proceed as follows to manually set the technology controller:
1. Temporarily set the ramp-up and ramp-down times of the ramp-function generator (p2257
and p2258) to zero.
2. Enter a setpoint step and monitor the associated actual value, e.g. with the trace function
of STARTER.
The slower the response of the process to be controlled, the longer you must monitor the
controller response. Under certain circumstances (e.g. for a temperature control), you
need to wait several minutes until you can evaluate the controller response.
3. Set the ramp-up and ramp-down times of the ramp-function generator back to their
original value.
You have now manually set the technology controller.
258
Optimum controller response for applications that do not per-
mit any overshoot.
The actual value approaches the setpoint without any signifi-
cant overshoot.
Optimum controller behavior for fast correction and quick com-
pensation of disturbance components.
The actual value approaches the setpoint and slightly over-
shoots, maximum 10% of the setpoint step.
The actual value only slowly approaches the setpoint.
Increase the proportional component K
integration time T
.
I
Actual value only slowly approaches the setpoint with slight
oscillation.
Increase the proportional component K
rate time T
(differentiating time).
d
The actual value quickly approaches the setpoint, but over-
shoots too much.
Decrease the proportional component K
integration time T
.
I
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
and reduce the
P
and reduce the
P
and increase the
P
SINAMICS G120C converter