Technical data
10.4 Power-dependent technical data
Table 10- 6
Frame size A, 3 AC 380 V ... 480 V, +10 %, -20 %
Article no.
Values for rated load/low overload
Rated/LO power
Rated/LO input current
Rated/LO output current
Values for high overload
HO power
HO input current
HO output current
Power loss with filter
Power loss without filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10- 7
Frame size B, 3 AC 380 V ... 480 V, +10 %, -20 %
Article no.
Values for rated load/low overload
Rated/LO power
Rated/LO input current
Rated/LO output current
Values for high overload
HO power
HO input current
HO output current
Power loss with filter
Power loss without filter
Required cooling air flow
Weight without filter
Weight with filter
362
Without filter, IP20
6SL3210-1KE17-5U*1
with filter, IP20
6SL3210-1KE17-5A*1
Without filter, IP20
6SL3210-1KE21-3U*1
with filter, IP20
6SL3210-1KE21-3A*1
6SL3210-1KE18-8U*1
6SL3210-1KE18-8A*1
3.0 kW
9.5 A
7.3 A
2.2 kW
8.2 A
5.6 A
0.136 kW
0.146 kW
0.132 kW
0.141 kW
5 l/s
1.7 kg
1.9 kg
6SL3210- 1KE21-7U*1
6SL3210-1KE21-7A*1
5.5 kW
16.5 A
12.5 A
4.0 kW
12.8 A
8.8 A
0.177 kW
0.244 kW
0.174 kW
9 l/s
2.3 kg
2.5 kg
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC
4.0 kW
11.4 A
8.8 A
3.0 kW
10.6 A
7.3 A
5 l/s
1.7 kg
1.9 kg
7.5 kW
21.5 A
16.5 A
5.5 kW
18.2 A
12.5 A
0.24 kW
9 l/s
2.3 kg
2.5 kg