Advanced commissioning
6.2 Inverter control
Procedure
Defining the function of an analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input based on its
index, e.g. parameter p0755[0] is assigned to analog input 0.
Table 6- 3
CI
p1070 Main setpoint
p1075 Supplementary setpoint
p1503 Torque setpoint
p1511 Supplementary torque 1
A complete list of the connector inputs is provided in the List Manual.
Defining the function of an analog input - example
138
Connector inputs (CI) of the inverter (selection)
Significance
Set the following parameters to set the analog input as
current input with monitoring:
1. Set p0756[0] = 3
This means that you define analog input 0 as current
input with wire breakage monitoring.
2. Set p0757[0] = 6.0 (x1)
3. Set p0758[0] = -100.0 (y1)
4. Set p0759[0] = 12.0 (x2)
5. Set p0760[0] = 100.0 (y2)
CI
Significance
p1522 Torque limit, upper
p2253 Technology controller setpoint 1
p2264 Technology controller actual value
To enter a supplementary setpoint via analog input AI 0,
you must interconnect AI 0 with the signal source for the
supplementary setpoint:
Set p1075 = 755[0].
Operating Instructions, 07/2015, FW V4.7 SP3, A5E34263257B AC