Power Supply Units
Power Supply Units
Removing and Installing Power Supply Units
In its basic configuration the system comes with two hot-swappable power
supply units. The power supply units automatically adjust to any power voltage
in the range (100 V - 127V or 200 V - 240 V).
Removal
Replace the defective power supply unit as soon as possible to restore
!
redundancy, avoid airflow disruption, satisfy cooling requirements and
comply with applicable EMC regulations.
The installation bay should not be vacant for more than five minutes while
the server is on. Exceeding the five-minute limit may cause damage to
certain components.
If one power supply unit has failed, do not remove any fan modules!
Requirements
Ê Check the FAN LED of the power supply units on the back of the system (see
page
02-BX600-34) to determine which power supply unit is defective.
Ê First disconnect the power supply cable of the defective PSU from the
mains.
Ê Remove the power supply cable from the insulated socket of the defective
PSU.
– the power cord of the defective power supply unit has been disconnected
Be careful! The PSU can be very hot!
!