Figure 22: Single Phase Pdu Outlet Groups - Oracle FS1-2 Installation Manual

Flash storage system
Hide thumbs Also See for FS1-2:
Table of Contents

Advertisement

Table 24: Single-phase PDUs (continued)
Single-phase
North America, South America,
PDUs
Japan, and Taiwan
Outlet groups
All PDUs have 42 outlets arranged
in six groups of seven outlets.
Receptacles
All 42 outlets are IEC60320 C13
style receptacles. The C13
receptacle can supply 10A.
Note: If two outlets are configured
to draw 10A each, the remaining
five outlets in the group cannot be
used.
Circuit breaker
Each group of seven outlets have a
20A rated circuit breaker that can
be re-set.
The following figure shows the outlet groups for single-phase PDUs.

Figure 22: Single phase PDU outlet groups

Legend
1 AC inlet circuit P1 supplies groups 0,1, and 2
2 AC inlet circuit P2 supplies groups 3,4, and 5
3 Current is monitored across both AC inlet circuits
System Power
EMEA
All PDUs have 42 outlets
arranged in six groups of seven
outlets.
All 42 outlets are IEC60320 C13
style receptacles. The C13
receptacle can supply 10A.
Note: If two outlets are
configured to draw 10A each,
the remaining five outlets in the
group cannot be used.
Each group of seven outlets have
a 20A rated circuit breaker that
can be re-set.
58