Pulse Outputs
5-2-7

Pulse Output Procedures

Single-phase Pulse Output without Acceleration/Deceleration
Determine the pulse output method,
output frequency, and port.
Wire the outputs.
PLC Setup settings
Ladder program
The number of output pulses setting cannot be changed during positioning.
PULS(886) and SPED(885)
• Pulse output method
• CW/CCW inputs: Pulse outputs 0 to 1
• Pulse + direction inputs: Pulse outputs 0 to 1
• Output frequency: 1 Hz to 100 kHz (1 Hz units)
J models: 1Hz to 20 kHz (1 Hz units)
• Enable/disable the origin search function. Set the
various origin search parameters if the origin search
function is enabled.
• PULS(886): Specify port number and set the number of
output pulses.
• SPED(885): Specify port number and set the output
method (CW/CCW method or Pulse + direction method)
and pulse output control without acceleration/deceleration.
• INI(880): Specify port number and stop pulse output when
necessary.
• PRV(881): Specify port number and read pulse output PV
when necessary.