Pulse Outputs
5-2-7
Pulse Output Procedures
Single-phase Pulse Output without Acceleration/Deceleration
Determine the pulse output method,
output frequency, and port.
Wire the outputs.
PLC Setup settings
Ladder program
The number of output pulses setting cannot be changed during positioning.
■
PULS(886) and SPED(885)
• Pulse output method
• CW/CCW inputs: Pulse outputs 0 to 1
• Pulse + direction inputs: Pulse outputs 0 to 1
• Output frequency: 1 Hz to 100 kHz (1 Hz units)
J models: 1Hz to 20 kHz (1 Hz units)
• Enable/disable the origin search function. Set the
various origin search parameters if the origin search
function is enabled.
• PULS(886): Specify port number and set the number of
output pulses.
• SPED(885): Specify port number and set the output
method (CW/CCW method or Pulse + direction method)
and pulse output control without acceleration/deceleration.
• INI(880): Specify port number and stop pulse output when
necessary.
• PRV(881): Specify port number and read pulse output PV
when necessary.
Section 5-2
239