Auxiliary Area Allocations by Function
Name
Error Counter
This flag turns ON when an error occurs in the error
Error Flag
counter for inverter positioning.
ON: Error counter error
OFF: No error
Error Counter
This flag is ON while pulses are being output to the out-
Pulse Output Flag
put counter for inverter positioning.
ON: Pulses being output
OFF: Pulse output stopped
Error Counter
This flag is ON while pulse output to the output counter
Pulse Output
for inverter positioning is accelerating or decelerating.
Accelera-
ON: Pulse output to the error counter is accelerating or
tion/Deceleration
decelerating (i.e., the frequency is changing)
Flag
OFF: Pulse output to the error counter is constant
Error Counter
This flag turns ON when an alarm occurs in the error
Alarm Flag
counter for inverter positioning.
ON: Error counter alarm
OFF: No alarm
Inverter Position-
This flag is ON when the inverter positioning output value
ing Output Value
is positive and is OFF when it is negative.
Sign Flag
ON: Positive value
OFF: Negative value
Error Counter
This word contains the present value of the error counter.
Present Value,
Data range: 8000 to 7FFF hex (−32,768 to 32,767)
Signed
Present Value of
These words contain the relative value of the internal
Pulse Output to
pulse output value when pulses are being output to the
Inverter, Relative
error counter.
Value
Data range: 8000 0000 to 7FFF FFFF hex
(−2,147,483,648 to 2,147,483,647)
Description
Read/Write
Read
• Turned OFF when power is turned
ON.
• Turned OFF when CPU Unit opera-
tion starts.
• Turned OFF when CPU Unit opera-
tion stops.
• Turned OFF when error counter
error is reset.
• Turned ON when pulse output to
error counter is stopped and abso-
lute value of error counter present
value is greater than or equal to
error counter error detection value.
Read
• Turned OFF when power is turned
ON.
• Turned OFF when CPU Unit opera-
tion starts.
• Turned OFF when CPU Unit opera-
tion stops.
• Turned OFF when error counter
error is reset.
• Turned ON when pulse output to
error counter is stopped and abso-
lute value of error counter present
value is greater than or equal to
error counter error detection value.
Read
• Turned OFF when power is turned
ON.
• Turned OFF when CPU Unit opera-
tion starts.
• Turned OFF when CPU Unit opera-
tion stops.
• Turned OFF during output of a con-
stant pulse frequency to error
counter.
• Turned OFF when pulse output to
error counter is stopped (including
immediate stops and deceleration
stops).
• Turned ON when pulse output fre-
quency to error counter is changed
by ACC or PLS2 instruction.
Read
• Turned OFF when power is turned
ON.
• Turned OFF when CPU Unit opera-
tion starts.
• Turned OFF when CPU Unit opera-
tion stops.
• Turned OFF when error counter
alarm is reset.
• Turned ON when pulse output to
error counter is stopped and abso-
lute value of error counter present
value is greater than or equal to
error counter alarm detection
value.
Read
• Turned ON when signed output
value is between 0000 0000 and
7FFF FFFF hex.
• Turned OFF when signed output
value is between FFFF FFFF and
8000 0000 hex.
Read
• Cleared when power is turned ON.
• Cleared when operation starts.
• Cleared when error counter is
reset.
• Held when Error Counter Disable
Bit (A562.01) is turned ON.
• Updated each error counter cycle.
Read
• Cleared when power is turned ON.
• Cleared when operation starts.
• Cleared when pulse output to error
counter is started.
• Updated each error counter cycle.
Appendix C
Updated
603