I/O Word Allocations To Expansion Units - Omron CP1L Operation Manual

Sysmac cp series
Hide thumbs Also See for CP1L:
Table of Contents

Advertisement

I/O Area and I/O Allocations
Input bits
Output bits
Input bits
Output bits
4-2-4

I/O Word Allocations to Expansion Units

Analog I/O Units
Analog Input Units
Analog Output Units
Temperature Sensor Units
DeviceNet I/O Link Units
CompoBus/S I/O Link
Units
Example 2: Connecting Expansion I/O Units with Only Inputs or Only
Outputs
If Expansion I/O Units with only inputs or only outputs are connected, the
input or output word not used by an Expansion I/O Unit is allocated to the next
Unit that requires it.
CPU Unit
(30 I/O points)
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.05
12 output points
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.03
Bit
15
14
13
12
CIO 0
CIO 1
Do not use.
CIO 2
CIO 3
CIO 100
CIO 101
Can be used as work bits.
CIO 102
CIO 103
CIO 104
Unit
CP1W-MAD11
CPM1A-MAD11
CPM1A-MAD01
CP1W-AD041
CPM1A-AD041
CP1W-DA041
CPM1A-DA041
CP1W-TS001
CPM1A-TS001
CP1W-TS002
CPM1A-TS002
CP1W-TS101
CPM1A-TS101
CP1W-TS102
CPM1A-TS102
CPM1A-DRT21
CP1W-SRT21
CPM1A-SRT21
m:
Indicates the next input word after the input word allocated to the
Expansion Unit, Expansion I/O Unit, or CPU Unit to the left of the cur-
rent Unit.
n:
Indicates the next output word after the output word allocated to the
Expansion Unit, Expansion I/O Unit, or CPU Unit to the left of the cur-
rent Unit.
First Expansion I/O Unit:
Second Expansion I/O Unit:
Unit with 8 inputs
Unit with 16 outputs
104.00 104.07
CIO 2.00 to CIO 2.07
16 output points
CIO 102.00 to CIO 102.07
CIO 103.00 to CIO 103.07
11
10
09
08
07
Third Expansion I/O Unit: Unit with 20 I/O
Input words
2 words CIO m to CIO m+1 1 word
4 words CIO m to CIO m+3 2 words CIO n to CIO n+1
None
---
2 words CIO m to CIO m+1 None
4 words CIO m to CIO m+3 None
2 words CIO m to CIO m+1 None
4 words CIO m to CIO m+3 None
2 words CIO m to CIO m+1 2 words CIO n to CIO n+1
1 word
CIO m
Third Expansion I/O Unit:
Unit with 20 I/O
CIO 3.00 to CIO 3.11
8 output points
CIO 104.00 to CIO 104.07
06
05
04
03
02
CPU Unit with 30 I/O points
First Expansion I/O Unit: Unit with 8 inputs
CPU Unit with 30 I/O
points
Second Expansion I/O Unit:
Unit with 16 outputs
Third Expansion I/O Unit: Unit with 20 I/O
Output words
CIO n
4 words CIO n to CIO n+3
---
---
---
---
1 word
CIO n
Section 4-2
01
00
151