Omron CP1L Operation Manual page 149

Sysmac cp series
Hide thumbs Also See for CP1L:
Table of Contents

Advertisement

Wiring CP1L CPU Units
Output Wiring Precautions
Output Short-circuit
Protection
Connecting to a TTL
Circuit
Inrush Current
Considerations
3. Relation between current when the PLC is OFF and sensor leakage cur-
rent:
≥ I
I
OFF
leak
Connect a bleeder resistor if I
equation to calculate the bleeder resistance constant.
R ≤ R
× V
/(I
IN
OFF
leak
Power W ≥ (V
− V
CC
Two-wire Sensor
Vcc: Power voltage
Von: PLC ON voltage
Voff: PLC OFF voltage
Ion: PLC ON current
Ioff: PLC OFF current
Rin: PLC input impedance
4. Precautions on Sensor Inrush Current
An incorrect input may occur due to sensor inrush current if a sensor is
turned ON after the PLC has started up to the point where inputs are pos-
sible. Determine the time required for sensor operation to stabilize after the
sensor is turned ON and take appropriate measures, such as inserting into
the program a timer delay after turning ON the sensor.
Program Example
In this example, the sensor's power supply voltage is provided to input bit CIO
0.00 and a 100-ms timer delay (the time required for an OMRON Proximity
Sensor to stabilize) is created in the program. After the Completion Flag for
the timer turns ON, the sensor input on input bit CIO 0.01 will cause output bit
CIO 100.00 to turn ON.
0.00
T100
0.01
If a load connected to the output terminals is short-circuited, output compo-
nents and the printed circuit boards may be damaged. To guard against this,
incorporate a fuse in the external circuit. Use a fuse with a capacity of about
twice the rated output.
A TTL circuit cannot be connected directly to a transistor output because of
the transistor's residual voltage. It is necessary to connect a pull-up resistor
and a CMOS IC between the two.
When connecting a transistor or triac output to a load having a high inrush
current (such as an incandescent lamp), steps must be taken to avoid dam-
age to the transistor or triac. Use either of the following methods to reduce the
inrush current.
is greater than I
leak
× R
− V
)
IN
OFF
2
/R × 4 (allowable margin)
)
R
R
V
R
IN
R
V
CC
Vr: Sensor output residual current
Iout: Sensor control output (load current)
Ileak: Sensor leakage current
R: Bleeder resistance
TIM
100
#0001
100.00
Section 3-4
. Use the following
OFF
DC Input Unit
115

Advertisement

Table of Contents
loading

Table of Contents