Omron CP1L Operation Manual page 293

Sysmac cp series
Hide thumbs Also See for CP1L:
Table of Contents

Advertisement

Pulse Outputs
Ladder Program
Jog Operation
Jogging
Switch
Jogging
Switch
Fixed-distance Feed
Positioning
Switch
Cutter
Finished
A280.03
Pulse Output
Completed Flag
Counting Feed Operations
A280.03
Pulse Output
Completed Flag
Positioning
Switch
Emergency
Stop
Settings for PLS2(887) for Fixed-distance Feeding (D10 to D20)
Acceleration rate: 1,000 Hz/4 ms
Deceleration rate: 1,000 Hz/4 ms
Target frequency: 10,000 Hz
Number of output pulses: 50,000 pulses
Starting frequency: 0000 Hz
Counter setting: 100 times
0.00
A280.04
Pulse Output
In-Progress
Flag
0.00
W0.00
Jogging
Flag
0.01
0.02
0.01
C0000
0.03
Setting details
SPED(885)
#0000
#0000
D0
SET W0.00
SPED(885)
#0000
#0000
D2
RSET W0.00
@PLS2(887)
#0000
#0000
D10
D16
100.02
CNT
0000
D20
100.03
INI(880)
#0000
#0003
Address
D10
D11
D12
D13
D14
D15
D16
D17
D20
Target frequency:
1,000 Hz
Jogging Flag
Target frequency:
0Hz
Jogging Flag
Cutter activated
Cutting Operation
Finished
0
Section 5-2
Data
03E8
03E8
2710
0000
C350
0000
0000
0000
0100
259

Advertisement

Table of Contents
loading

Table of Contents