Analog Output Units - Omron CP1L Operation Manual

Sysmac cp series
Hide thumbs Also See for CP1L:
Table of Contents

Advertisement

Analog Output Units

Analog Output Signal
Ranges
■ −10 to 10 V
The hexadecimal values F448 to 0BB8 (–3000 to 3000) correspond to an ana-
log voltage range of –10 to 10 V. The entire output range is –11 to 11 V. Spec-
ify a negative voltage as a two's complement.
F31C
F448
8000
(3300)
(3000)
■ 0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 0 to 10 V. The entire output range is –0.5 to 10.5 V. Specify a
negative voltage as a two's complement.
FED4
8000
(−300)
■ 1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
8000
11 V
10 V
0000 (0)
0BB8
0CE4
0 V
(3000)
(3300)
−10 V
−11 V
10.5 V
10 V
0000 (0)
1770
189C
0 V
(6000)
(6300)
−0.5 V
5.2 V
5 V
1 V
0.8 V
1770
189C
FED4
0 V
(6000)
(6300)
(−300)
Section 7-3
Conversion
Data
7FFF
Hexadecimal
(Decimal)
Conversion
Data
7FFF
Hexadecimal
(Decimal)
Conversion
Data
7FFF
Hexadecimal
(Decimal)