Section 6-2

Linear Output Range

This setting is only for Models with 4 to 20 mA, 1 to 5 V linear output.
Output
Linear scaling (for 4 to 20 mA output)
(mA)
Displayed value
For operating parameters 1 through 3, the Intelligent Signal Processor out-
puts a linear voltage or current in proportion to the changes in the measured
value. In the example above, a displayed value corresponding to the L
max-
H
imum output value (20 mA or 5 V) and a displayed value corresponding to
the L
minimum output value (4 mA or 1 V) is set.
L
The decimal is displayed at the position set in the prescale parameter. Note
that neither L
nor L
shift if the position of the decimal is changed after L
H
L
H
and L
have been set.
L
Do not set L
= L
; otherwise, it is assumed that L
+ 1 digit = L
.
L
H
L
H
This function is not provided on the mV/digit Output Models on which regard-
less of the position of the decimal, 1 mVDC is output per digit displayed. (For
example, if the displayed value is 150.0, the output is 1500 mV.) A linear out-
put range cannot be set with Thumbwheel Switches Models.
In order to set the linear output range, follow the instructions outlined in the
flow diagram and operate the Intelligent Signal Processor as follows: