DeviceNet I/O Link Units

7-7
DeviceNet I/O Link Units
DeviceNet slave
Master PLC (CS Series with fixed allocations)
CPU Unit
Outputs
CIO 50
CIO 51
Inputs
CIO 350
CIO 351
482
Connecting a CPM1A-DRT21 DeviceNet I/O Link Unit (with 32 inputs and 32
outputs as built-in I/O) to function as a slave allows the CP1L to be used as a
DeviceNet slave. A maximum of three DeviceNet I/O Link Units can be con-
nected to the CP1L to create I/O Links for up to 192 points (96 inputs and 96
outputs) between the CP1L and the DeviceNet master.
PLC supporting DeviceNet
master, e.g., CS, C200HX/HG/HE
(-Z), CVM1, CV-series, etc.
DeviceNet Master Unit or
DeviceNet Unit
SYSMAC
CP1L
IN
L1
L2/N
COM
01
03
05
07
09
11
01
03
05
00
02
04
06
08
10
00
02
04
00
01
02
03
04
06
00
01
COM
COM
COM
COM
05
07
COM
02
OUT
CP1H CPU Unit
From the standpoint of the CP1L CPU Unit, the 32 input bits and 32 output
bits allocated to the DeviceNet I/O Link Unit are identical to input and output
bits allocated to Expansion I/O Units even though the DeviceNet I/O Link Unit
does not control external inputs and outputs. The input and output bits allo-
cated to the DeviceNet I/O Link Unit are one side of an I/O link between the
slave CPU Unit and the CP1L CPU Unit to which the Master Unit is con-
nected.
DeviceNet
Master Unit
I/O memory
Unit No. 0
32 bits
32 bits
Note
Refer to the DeviceNet Slaves Operation Manual (W347) for details on
DeviceNet networks.
Specifications
Model number
Master/slave
DeviceNet transmission path
07
09
11
06
08
10
03
04
06
COM
05
07
CPM1A-DRT21
DeviceNet I/O Link Unit
CPU Unit
I/O memory
CPM1A-DRT21
DeviceNet Slave
DeviceNet slave
Each Unit enables remote I/O
communications for 32 input and 32
output points as a DeviceNet slave.
CP1L
DeviceNet
I/O Link Unit
Node
number: 0
Inputs
CIO 2
32 bits
CIO 3
Outputs
CIO 12
32 bits
CIO 13
Section 7-7