Temperature Sensor Units
Two-decimal-place
Mode
Programming with SCL2(−) Instruction
Always ON
P_On
Execution
1000.00
condition
Operation
CIO 2
16
3
16
D1
0
If pin 2 on the DIP switch is turned ON, values are stored to two decimal
places. In this case, temperature data is stored as 6-digit signed hexadecimal
(binary) data with 4 digits in the integer portion and 2 digits after the decimal
point. The actual data stored in memory is 100 times the actual value, i.e., the
decimal point is not indicated. Methods for handling this data are described in
this section.
Note
When set to store values to two decimal places, temperature data as far as
two digits after the decimal point is converted to 6-digit binary data, but the
actual resolution is not 0.01°C (°F). For this reason, there may be skipping
and inaccuracies in the first digit after the decimal point (0.1). Treat any reso-
lution above that specified for the normal data format as reference data.
P_EQ
P_EQ
P_CY
P_CY
Binary to BCD conversion
2
16
1
16
0
0
0
1/0
1: Negative, 0: Non-negative
0: If data non-negative, "0000" stored in D1.
1: If data negative, "0001" stored in D1.
Detects completion of input 0
CMP(020)
initialization.
2
#7FFE
1000.00
ON when initialization complete.
CMP(020)
Detects an open-circuit alarm.
2
#7FFF
ON when an open-circuit alarm has
01000
been detected.
SCL2(486)
2
D10
Parameter settings for data conversion:
D0
MOV(021)
When the converted value is non-
negative, stores #0000 in D00001.
#0000
D1
MOV(021)
When the converted value is
negative, stores #0001 in D00001.
#0001
D1
CY
(when using SCL2 instruction)
D0
10
3
10
2
10
1
10
0
1/0
Section 7-5