Analog Input Units
Item
Number of inputs
Input signal range
Max. rated input
External input impedance
Resolution
Overall accuracy
25°C
0 to 55°C
A/D conversion data
Averaging function
Open-circuit detection function
Conversion time
Isolation method
Current consumption
Analog Input Signal
Ranges
4 inputs (4 words allocated)
0 to 5 VDC, 1 to 5 VDC,
0 to 10 VDC, or –10 to 10 VDC
±15 V
1 MΩ min.
1/6000 (full scale)
0.3% full scale
0.6% full scale
16-bit binary (4-digit hexadecimal)
Full scale for –10 to 10 V: F448 to 0BB8 Hex
Full scale for other ranges: 0000 to 1770 Hex
Supported (Set in output words n+1 and n+2.)
Supported
2 ms/point (8 ms/all points)
Photocoupler isolation between analog I/O terminals and internal circuits. No isolation
between analog I/O signals.
5 VDC: 100 mA max.; 24 VDC: 90 mA max.
Analog input data is digitally converted according to the input signal range as
shown below.
Note
When the input exceeds the specified range, the A/D conversion data will be
fixed at either the lower limit or upper limit.
Voltage Input
Current Input
0 to 20 mA or 4 to 20 mA
±30 mA
Approx. 250 Ω
0.4% full scale
0.8% full scale