Mounting
DIN Track
2. Lower the Units so that they catch on the top of the DIN Track, and then
press them forward all the way to the DIN Track at the bottom.
3. Press in all of the DIN Track mounting pins to securely lock the Units in
place.
Mount the DIN Track in the control panel with screws in at least three places.
• DIN Track: PFP-50N (50 cm), PFP-100N (100 cm), or PFP-100N2
(100 cm)
Secure the DIN Track to the control panel using M4 screws separated by
210 mm (6 holes). The tightening torque is 1.2 N·m.