14.5 Closing the high-voltage door

Instruction label on high-voltage door:
In addition to these instructions, an instruction label on the high-voltage door describes safe closing of the
high-voltage door before executing a switching operation.
Fig. 264: Instruction label on high-voltage door
Preconditions
Contactor truck:
Contactor truck removed from the panel
or
Contactor truck inserted in test position
High-voltage door open
Padlock for door handle (optional) available
Procedure
Push the door handle on the high-voltage door totally upwards, and hold it.
Press the high-voltage door totally onto the panel frame using the door handle.
110-0134.9 / 14
Operating the contactor panel with panel width 600 mm
WARNING
Reduced safety
The closed high-voltage door is an important safety element of the switchgear.
The high-voltage door is exclusively opened for performing operational activities
inside the switching-device compartment, such as removing or inserting a
contactor truck.
Close the high-voltage door:
If an activity inside the switching-device compartment is interrupted.
Immediately after an activity inside the switching-device compartment was
completed.
Before leaving the panel front.
NXAIR / ≤ 40 kA
151