Operating the contactor panel with panel width 600 mm

14.11 Opening the contactor manually

Preconditions
Contactor truck in service position or in test position
Contactor in CLOSED position
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
High-voltage door closed
Panel set to local control
Double-bit key available
162
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For operating the contactor manually, set the panel to local control, for
example by switching the local-remote switch to LOCAL position.
INFORMATION
Unexpected switching noise and vibration
Operating the contactor causes a short loud noise and low vibration.
Expect switching noise and low vibration from inside the contactor.
INFORMATION
Manual operation of the contactor is limited to manual opening of the contactor.
Manual closing of the contactor is not possible.
INFORMATION
Contactor truck version with mechanical closing latch
Opening the contactor also opens the closing latch.
NXAIR / ≤ 40 kA
110-0134.9 / 14