Taking The Removable Voltage Transformers Out Of The Panel - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Fig. 444: Removing the racking tool
To close the actuating opening, push the operating slide down as far as it will go.
Fit a padlock to the operating slide and close it.
Fig. 445: Fitting a padlock
The removable voltage transformers are in test position.

19.6 Taking the removable voltage transformers out of the panel

Preconditions
High-voltage door closed
Removable voltage transformers in test position
Door to voltage transformer compartment open
Service truck available
Removing the low-voltage connector
To detach the low-voltage connector, push the longitudinal fastener (1) of the coupling
downwards.
Remove the low-voltage connector (2) carefully upwards.
110-0134.9 / 14
Operating the removable voltage transformers
NXAIR / ≤ 40 kA
249