Siemens NXAIR Operating Instructions Manual page 345

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Install the labyrinth.
Fig. 639: Labyrinth installed, front
Fix the labyrinth by screwing the outermost nuts hand-tight:
2 nuts M8 with contact washers
Tighten the nuts with a tightening torque of 25 Nm.
Fig. 641: 2 bolted joints at front of labyrinth
Tighten the fixing bolts at the top side of the labyrinth hand-tight:
4 bolts M8x16 with contact washers
Tighten the bolts with a tightening torque of 25 Nm.
Fig. 642: 4 bolted joints at top side of labyrinth
110-0134.9 / 14
Accessing the connection compartment through the front
Fig. 640: Labyrinth installed, top side
NXAIR / ≤ 40 kA
345