Siemens NXAIR Operating Instructions Manual page 259

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Selection table for protection fuse-links:
Rated voltage U
7.2
12
17.5
Supplier information :
Alternative supplier for fuse-links:
Rated voltage U
7.2
12
17.5
Supplier information :
Removable voltage transformer rating plate
Further technical data is shown on the rating plate of each removable voltage transformer.
Fig. 469: Rating plate on removable voltage transformers
110-0134.9 / 14
Operating the removable voltage transformers
INFORMATION
A tripped protection fuse-link can cause hidden damages on the other protection
fuse-links.
Always replace all protection fuse-links, even if only one protection
fuse-link has tripped.
[kV]
Supplier:
r
SIBA
SIBA
SIBA
www.siba-fuses.com
[kV]
Supplier:
r
Inter-Teknik
Inter-Teknik
Inter-Teknik
www.inter-teknik.com
NXAIR / ≤ 40 kA
Order details:
3000211.2/ 2 A / 192 mm
3011911.2/ 2 A / 192 mm
3017911.2 / 2 A / 192 mm
Order details:
S1Z1002 / 2 A / 192 mm
+S1Z.12KV.192.002 / 2 A / 192 mm
+S1Z.17.5KV.192.002 / 2 A / 192 mm
259