Lower the ramps (1) of the panel base.
1
Fig. 225: Lowering the ramps
Unlocking the contactor truck from the panel
Release the interlocking with the panel by turning the two locking levers at the contactor
truck to the outside.
Fig. 227: Releasing the interlocking
110-0134.9 / 14
Operating the contactor panel with panel width 435 mm
CAUTION
Sharp edges
The metal parts of the contactor truck may have sharp edges.
Put on personal protective equipment.
with the panel
NXAIR / ≤ 40 kA
Fig. 226: Ramps in open position
Fig. 228: Contactor truck unlocked