Siemens NXAIR Operating Instructions Manual page 123

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Preconditions
Authorization to operate the manual unlocking available
Auxiliary voltage for the panel disconnected
High-voltage door closed
Contactor truck in service position
Contactor in CLOSED position or OPEN position
Key for padlock available
Double-bit key available
Racking crank available
Procedure
Make sure to operate the particular contactor panel authorization is given for.
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
Fig. 203: Lifting the operating slide
Insert the double-bit key without turning.
Fig. 204: Double-bit key inserted
110-0134.9 / 14
Operating the contactor panel with panel width 435 mm
NXAIR / ≤ 40 kA
123