Fig. 661: Rear ledges and rear walls on
Remove the connecting elements from the horizontal ledge (3):
12 / 14 bolts M8x20 with contact washers
Remove the horizontal ledge and store it together with the associated connecting elements.
Remove the connecting elements from one of the vertical ledges (5):
9 / 19 bolts M8x20 with contact washers and plain washers size 8
acc. to ISO 7093
Remove the vertical ledge and store them together with the associated connecting elements.
Proceed in the same way with the other vertical ledges.
Loosen the connecting elements for the lower rear wall at the panel bottom (6):
4 / 6 bolts M8x20 with contact washers
Remove the lower rear wall (4). To do this, lift the rear wall by the handle, and pull it out. Store
the rear wall.
Loosen the connecting elements for the upper rear wall in the upper area (1):
4 / 5 bolts M8x20 with contact washers
110-0134.9 / 14
Accessing the connection compartment through the rear
connection duct
NXAIR / ≤ 40 kA
1
2
(1)
Bolted joints for upper rear wall
3
(2)
Upper rear wall with handle
(3)
Horizontal ledge
(4)
Lower rear wall with handle
(5)
Vertical ledges
4
(6)
Bolted joints for lower rear wall
5
6