Siemens NXAIR Operating Instructions Manual page 126

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the contactor panel with panel width 435 mm
Instruction label on high-voltage door:
In addition to these instructions, an instruction label on the high-voltage door informs about proper operation
of the operating lever for the feeder earthing switch.
Fig. 211: Instruction label on high-voltage door
Preconditions
High-voltage door closed
Contactor truck in test position
Feeder to be earthed isolated
Padlock (optional) removed from operating slide
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
Operating lever available
Procedure
To release the actuating opening, lift the operating slide and hold it.
Insert the operating lever in the actuating opening as far as it will go.
Turn the operating lever clockwise 180° until the feeder earthing switch changes to
CLOSED position.
Fig. 213: Lifting the operating slide
126
Fig. 212: Operating lever
Fig. 214: Inserting the operating lever
NXAIR / ≤ 40 kA
110-0134.9 / 14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents