Earthing And De-Earthing The Busbar System; Earthing The Busbar System Manually - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Earthing and de-earthing the busbar system

21 Earthing and de-earthing the busbar system

21.1 Earthing the busbar system manually

Arrangement of control elements
The operating mechanism of the earthing switch provided for earthing the busbar system is located in the
front upper area of the low-voltage compartment.
Fig. 497: Control elements of earthing switch
110-0134.9 / 13
INFORMATION
Read and understand these instructions before attempting operating works.
for busbar system
WARNING
Risk of falling
Falling from a ladder can lead to injuries and bone fractures.
Observe the guidelines for the use of working materials.
Use approved electrician's ladders only.
Observe the manual and the instructions on the ladder.
NOTICE
Maloperation
A switching operation once started must be completed totally! A switching
operation that was not completed cannot be turned back.
Do not try to remove the operating lever at intermediate positions.
NXAIR / ≤ 40 kA
273

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents