Siemens NXAIR Operating Instructions Manual page 341

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Fig. 629: 11 bolted joints on bushing plate
Fix the connecting leads (4). To do this, mount the connecting elements (3) and tighten
hand-tight:
3 nuts M8 with contact washers and plain washers
Tighten the nuts with a tightening torque of 25 Nm.
Fig. 630: 3 bolted joints at the cable connections (central joint covered)
Install the vertical partition in the connection compartment.
110-0134.9 / 14
Accessing the connection compartment through the front
NXAIR / ≤ 40 kA
1
2
341