Operating the circuit-breaker panel

10.22 Taking the circuit-breaker truck out of the panel

Fig. 144: Circuit-breaker panel with high-voltage door open
Preconditions
Circuit-breaker truck in test position
Spring energy store in the circuit-breaker discharged
High-voltage door open
Low-voltage connector stowed away
86
CAUTION
Injury
The mechanism inside the circuit-breaker truck can cause injuries by getting
squeezed, caught or cut.
Do not remove any parts of the covering.
Do not charge the spring energy store in the circuit-breaker.
NXAIR / ≤ 40 kA
110-0134.9 / 14