19.3 Closing the door to the voltage transformer compartment

Preconditions
High-voltage door closed
Door to voltage transformer compartment open
If removable voltage transformers inserted: low-voltage connector plugged on
Hexagon socket head key size 6 available
Padlock available
Procedure
Close the door to the voltage transformer compartment using the handle (2).
Screw in 3 hexagon socket head bolts (1) hand-tight using the hexagon socket head key.
This corresponds to a tightening torque of approx. 20 Nm.
Fit the padlock (3) to the operating slide and close it.
Fig. 427: Closing the door to the voltage transformer compartment
The door to the voltage transformer compartment is closed.
110-0134.9 / 14
Operating the removable voltage transformers
WARNING
Electric shock
Do not operate the panel with the door to the voltage transformer
compartment open.
Always secure the closed door to the voltage transformer compartment
with the bolts.
INFORMATION
The door to the voltage transformer compartment is not linked with the
high-voltage door.
The door to the voltage transformer compartment can be operated
independently of the high-voltage door.
NXAIR / ≤ 40 kA