Operating the contactor panel with panel width 435 mm

13.7 Racking the contactor truck to service position

Preconditions
Contactor truck in test position
Low-voltage connector plugged on (automatically)
High-voltage door closed
Contactor in OPEN position
Feeder earthing switch in OPEN position
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
Racking crank for moving the contactor truck available
Double-bit key available
Padlock (optional) removed from operating slide
Fig. 183: Racking crank
Procedure
114
NOTICE
Maloperation
Racking the contactor truck to service position is only permissible if the contactor
is in OPEN position.
Switch the contactor to OPEN position, if required.
NOTICE
Maloperation
All interlocks are only released when the contactor truck is in a stable end
position.
Rack the contactor truck absolutely until end position.
NXAIR / ≤ 40 kA
Fig. 184: Double-bit key with
a diameter of 5 mm
110-0134.9 / 14