Siemens NXAIR Operating Instructions Manual page 106

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the metering panel
Pull the upper end of the protection fuse-link off the clamp.
Pull the lower end of the protection fuse-link off the clamp and remove the protection fuse-
link.
Fig. 171: Pulling off the fuse-link
Push the lower end of the new protection fuse-link into the clamp.
Push the upper end of the new protection fuse-link into the clamp.
Perform replacement with all other fuse-links.
The protection fuse-links have been replaced.
106
INFORMATION
Final procedure steps
Next, insert the withdrawable metering part / metering truck into the panel.
After closing the high-voltage door, the panel can be integrated into the
course of operation again.
NXAIR / ≤ 40 kA
110-0134.9 / 14