Siemens NXAIR Operating Instructions Manual page 384

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Panels with motor operating mechanism control
The following table gives an overview of the possible access mode indications, the corresponding operating
options and their preconditions.
Indication
Access mode
Access is released for
motor-operated racking
Preconditions for operating options:
Low-voltage connector plugged on
High-voltage door closed
Feeder earthing switch in OPEN position
Circuit-breaker in OPEN position
Control door closed and padlocked
Local or remote control
Access is released for manual racking
Preconditions for operating options:
High-voltage door closed
Feeder earthing switch in OPEN position
Circuit-breaker in OPEN position
Panel set to local control
Control door open
Racking interlocked
Preconditions for operating options:
Circuit-breaker in OPEN position
Withdrawable circuit-breaker / circuit-breaker truck in test position
Panel set to local control
384
INFORMATION
Blocking any racking operation is the precondition for opening the high-voltage
door.
Before opening the high-voltage door, set the access mode indicator to
"T".
NXAIR / ≤ 40 kA
Operating options
Racking the withdrawable circuit-breaker / circuit-
breaker truck electrically from test position to
service position, or from service position to test
position
Racking the withdrawable circuit-breaker / circuit-
breaker truck manually from test position to service
position, or from service position to test position
Closing the control door
Opening the high-voltage door
Taking the withdrawable circuit-breaker /
circuit-breaker truck out of the panel
110-0134.9 / 14