Siemens NXAIR Operating Instructions Manual page 140

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the contactor panel with panel width 435 mm
Permissible HV HRC fuse-links
The specified SIBA HV HRC fuse-links are motor protection back-up fuse-links according to IEC 60282-1.
The dimensions of the HV HRC fuse-links correspond to DIN 43625.
Selection table for HV HRC fuse-links
Rated
Rated current
voltage
I
[A]
r
U
[kV]
r
50
63
80
100
7.2
125
160
200
250
315
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com
Rated
Rated current
voltage
I
[A]
r
U
[kV]
r
50
63
80
12
100
125
160
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com
140
NOTICE
Maloperation
Contactor trucks are exclusively designed for operation with specific HV HRC
fuse-links. Using other types of fuse-links may cause damages on the panel.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of HV HRC fuse-links.
Number of
Dimension
fuse-links
"e" [mm]
permitted per
442
Number of
Dimension
fuse-links
"e" [mm]
permitted per
442
NXAIR / ≤ 40 kA
Order details
(SIBA)
phase
3010853.50
1
1
3010853.63
3010853.80
1
1
3010853.100
3010953.125
1
1 or 2
3010953.160
1 or 2
3011054.200
3011054.250
1 or 2
1
3011054.315
Order details
(SIBA)
phase
1
3010153.50
1
3010153.63
1
3010253.80
1
3010253.100
3010253.125
1 or 2
1 or 2
3010353.160
Order details
(Inter-teknik)
+S68T.12KV.442.050.08-7.2
+S68T.12KV.442.063.08-7.2
+S68T.12KV.442.080.08-7.2
+S4T.12KV.442.100.08-7.2
+S4T.12KV.442.125.08-7.2
+S4T.12KV.442.160.08-7.2
+S4T.12KV.442.200.08-7.2
+S4T.12KV.442.250.08-7.2
+S4T.12KV.442.315.08-7.2
Order details
(Inter-teknik)
+S68T.12KV.442.050.08
+S68T.12KV.442.063.08
+S68T.12KV.442.080.08
+S4T.12KV.442.100.08
+S4T.12KV.442.125.08
+S4T.12KV.442.160.08
110-0134.9 / 14