Siemens NXAIR Operating Instructions Manual page 326

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Accessing the connection compartment through the front
Preconditions
Preparations as described in chapter 23.1 completed
Fig. 602: Panel prepared
Procedure
Remove the connecting elements (2) from the protection plate (1), and store it:
4 nuts M8 with contact washers
Remove the protection plate (1), and store it.
Fig. 603: 4 bolted joints on protection plate
Remove the connecting elements from the front part (3) of the ventilation duct, and store it:
8 bolts M8x20 with contact washers
326
NXAIR / ≤ 40 kA
1
2
110-0134.9 / 14