Key-Operated Interlocks For The Busbar Earthing Switch - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Key-operated interlocks

25.2 Key-operated interlocks for the busbar earthing switch

Function and design
Key-operated interlocks are available for circuit-breaker and disconnecting panels. Access to the key of any
interlock is given with closed door to low-voltage compartment.
Key-operated interlocks allow interlocking or releasing the following operating functions:
If the busbar earthing switch is in OPEN position, switching it to CLOSED position can be interlocked
by turning and removing the associated key.
If the busbar earthing switch is in CLOSED position, switching it to OPEN position can be interlocked
by turning and removing the associated key.
The interlocked functions can be released again by reinserting the associated key, and subsequently turning
it in opposite direction.
For customization, the interlocking options are available individually. In case of two interlocks, removing both
keys simultaneously is not possible because the busbar earthing switch must always be either in CLOSED
position or OPEN position.
1
2
Fig. 667: Door to low-voltage compartment with key-operated interlocks
368
2
2
NXAIR / ≤ 40 kA
Key release:
only when busbar
(1)
earthing switch is in
OPEN position
Key release:
only when busbar
(2)
earthing switch is in
CLOSED position
110-0134.9 / 14