Siemens NXAIR Operating Instructions Manual page 186

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the contactor panel with panel width 600 mm
Preconditions
Contactor truck with the same coding as panel available
Coupling pin of the operating shaft in vertical position
High-voltage door open
Low-voltage connector stowed away
Auxiliary voltage for the panel disconnected
Fig. 334: Panel prepared to insert contactor truck
Procedure
Move the contactor truck centrally in front of the panel. The rollers (1) of the contactor truck
point towards the guide rails (2) at the bottom of the panel.
Fig. 335: Contactor truck in front of panel
186
NXAIR / ≤ 40 kA
110-0134.9 / 14