Siemens NXAIR Operating Instructions Manual page 366

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Key-operated interlocks
Fig. 664: Example: Cover lifted (circuit-breaker panel width 600 mm)
Fig. 665: Example: Cover lifted
(circuit-breaker panel width 800 / 1000 mm)
366
(1) Cover, lifted
(2) Screw thread for rotary button
Key release:
(3)
Only when feeder earthing switch is in
CLOSED position
Key release:
Only when feeder earthing switch is in
(4)
OPEN position
Key release:
(5)
Only when withdrawable part / switching-
device truck is racked to test position
NXAIR / ≤ 40 kA
110-0134.9 / 14