Operating the busbar connection panel type I

15.3 Access to compartments

Regarding accessibility to the individual compartments, NXAIR switchgear fulfills the loss of service
continuity category LSC 2B according to IEC 62271-200.
The degree of protection between the individual compartments is IP2X.
The type of accessibility is provided as follows:
Compartment
Switching-device compartment
Busbar compartment
Access from the front side
Connection
compartment
Access from the rear side

15.4 Opening or closing the high-voltage door

The procedure for opening and/or closing the high-voltage door at the busbar connection panel type I is
identical with the procedure for opening and/or closing the high-voltage door at the circuit-breaker panel.
For opening and/or closing the high-voltage door at the busbar connection panel type I,
see chapter 10.4 and/or 10.5.

15.5 Racking the withdrawable metering part / metering truck

The procedure for racking the withdrawable metering part / metering truck to service position and/or test
position is identical with the procedure for racking the withdrawable circuit-breaker / circuit-breaker truck to
service position and/or test position.
For racking the withdrawable metering part / metering truck to service position and/or test
position, see chapter 10.8 and/or 10.9.

15.6 Removing or plugging on the low-voltage connector

The
procedure
for
busbar connection panel type I is identical with the procedure for removing and/or plugging on the
low-voltage connector in the circuit-breaker panel.
Control elements at the front side of the withdrawable metering part / metering truck
Access to the control elements at the front side of the withdrawable metering part / metering truck is given
after opening the high-voltage door.
Fig. 364: Control elements at the front of the withdrawable metering part / metering truck, example
204
removing
and/or
plugging
(1) Miniature circuit-breakers
NXAIR / ≤ 40 kA
Type of accessibility
Interlock-controlled
Tool-based
Interlock-controlled and tool-based
Tool-based
on
the
low-voltage
connector
in
the
1