Operating the circuit-breaker panel
Pull the circuit-breaker truck out of the panel using the handles.
Fig. 148: Pulling out the circuit-breaker truck
If no further operation is executed: Close the high-voltage door.
The circuit-breaker truck can now be moved away from the panel.
88
CAUTION
Maloperation
Protruding parts at the rear of the circuit-breaker truck can cause injuries.
Move and operate the circuit-breaker truck only at the front side.
NOTICE
Maloperation
The locking bracket at the circuit-breaker truck is exclusively designed for
interlocking the circuit-breaker truck with the switchgear frame.
Do not push the locking bracket downwards towards LOCK if the circuit-
breaker truck is outside the panel.
NXAIR / ≤ 40 kA