Operating the removable voltage transformers
Preconditions
High-voltage door closed
Door to voltage transformer compartment closed
If inserted: removable voltage transformers in test position
Hexagon socket head key size 6 available
Key for padlock available
Procedure
Remove the padlock from the operating slide (3).
Undo 3 hexagon socket head bolts (1). The bolts remain permanently in the door to the
voltage transformer compartment.
Open the door to the voltage transformer compartment using the handle (2).
Fig. 425: Opening the door to the voltage transformer compartment
Fig. 426: Door to the voltage transformer compartment open
The door to the voltage transformer compartment is open.
240
INFORMATION
The door to the voltage transformer compartment is not linked with the high-
voltage door.
The door to the voltage transformer compartment can be operated
independently of the high-voltage door.
NXAIR / ≤ 40 kA
110-0134.9 / 14