Siemens NXAIR Operating Instructions Manual page 364

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Accessing the connection compartment through the rear
Fig. 662: Rear ledges and rear walls
Install the horizontal ledge (3). Fix it by screwing the bolts hand-tight:
12 / 14 bolts M8x20 with contact washers; use washers size 8
acc. to ISO 7093 with the bolt fixing in the area of the vertical ledges
Tighten the bolts with a tightening torque of 25 Nm.
The rear walls are installed on the connection duct.
364
on connection duct
INFORMATION
Final procedure steps
Now the panel can be integrated into the course of operation again, for example:
De-earthing the feeder.
Racking the withdrawable part / switching-device truck to service position.
NXAIR / ≤ 40 kA
1
Bolted joints for
(1)
2
upper rear wall
Upper rear wall
(2)
3
with handle
(3)
Horizontal ledge
Lower rear wall
(4)
with handle
4
(5)
Vertical ledges
Bolted joints for
(6)
lower rear wall
5
6
110-0134.9 / 14