Siemens NXAIR Operating Instructions Manual page 372

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Fitting the earthing device
Preconditions
Withdrawable part / switching-device truck taken out of the panel
Low-voltage connector stowed away
Both shutter to the connection compartment and shutter to the busbar compartment closed
Bushing contacts to be earthed isolated
Earthing device accessories available and in perfect condition
All panel versions except for contactor panels with 435 mm width:
Slip-on lever for opening the shutter available
Padlock for shutter not to be used available
Personal protective equipment put on
Fig. 675: Panel prepared
372
DANGER
Impermissibly high voltage and current
Inappropriate use of the earthing device accessories will result in impermissibly
high voltage and current.
Use the earthing device exclusively for the maximum permissible short-
circuit current and the maximum permissible short-circuit duration.
Do not use the earthing device for short-circuit tests or purposes causing
similarly high voltages and currents.
Perform diligent inspection of the earthing device accessories before
each application.
NXAIR / ≤ 40 kA
Upper shutter covering
(1)
bushing contacts linked
1
with busbar compartment
Lower shutter covering
(2)
bushing contacts linked with
2
connection compartment
Fig. 676: Fixed earthing point for
connecting the
earthing clamp
110-0134.9 / 14