Siemens NXAIR Operating Instructions Manual page 288

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the shutters
Operate the slip-on lever outside the panel using the handle: Push the handle downwards as
far as it will go. The slip-on lever latches tight and the shutter opens.
Fig. 530: Pushing on the slip-on lever
Fig. 532: Shutter to the connection compartment open
The shutter to the connection compartment is open.
288
INFORMATION
Final procedure steps
Immediately proceed to perform a voltage test with recommended suitable
equipment or other intended operations.
NXAIR / ≤ 40 kA
Fig. 531: Pushing the handle downwards
to end position
110-0134.9 / 14