Siemens NXAIR Operating Instructions Manual page 94

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the circuit-breaker panel
Preconditions
Panel prepared, no circuit-breaker truck inserted
Circuit-breaker truck with the same coding as panel available
Coupling pin of the operating shaft in vertical position
Spring energy store in the circuit-breaker discharged
High-voltage door open
Low-voltage connector stowed away
Auxiliary voltage for the panel disconnected
Fig. 155: Panel prepared to insert circuit-breaker truck
Procedure
Move the circuit-breaker truck centrally in front of the panel. The rollers (1) of the circuit-
breaker truck point towards the guide rails (2) at the bottom of the panel.
Push the circuit-breaker truck into the panel as far as it will go.
Fig. 156: Circuit-breaker truck in front of panel
94
NXAIR / ≤ 40 kA
110-0134.9 / 14