Procedure
Approaching from either the left or right side of the contactor truck, first pull the upper end
of the protection fuse-link off the clamp. Second, pull the lower end off the clamp and
remove the protection fuse-link.
Fig. 358: Pulling the upper end
Push the ends of the new protection fuse-link into the lower and upper clamp.
Pull the ends slightly to check if the protection fuse-link is inserted firmly.
Fig. 360: Pushing the upper end
110-0134.9 / 14
Operating the contactor panel with panel width 600 mm
NXAIR / ≤ 40 kA
Fig. 359: First protection fuse-link removed
Fig. 361: First protection fuse-link replaced