Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

3

Features

The air-insulated medium-voltage switchgear type NXAIR has the following features:
Factory-assembled, type-tested, metal-enclosed and metal-clad switchgear for indoor installation
Type of accessibility A
Internal arc classification (IAC): IAC A FLR ≤ 40 kA 1 s or IAC A FL ≤ 40 kA 1 s according to
IEC 62271 Part 200
Loss of service continuity category: LSC 2B (metal-clad) and LSC 2A (swtich-disconnector panel)
Partition class: PM (metallic partition) and PI (shutter made of insulation material for switch-
disconnector panel)
All switching operations can be carried out at the panel front with the high-voltage door closed
Standard degree of protection IP3XD for the metal enclosure according to IEC 60529
Metallic, positively driven shutters protect against accidental contact with live parts inside the panel
Logical interlock between actuation, circuit-breaker, switch-fuse combination, disconnecting function
and feeder earthing switch operating mechanism prevent maloperation
Earthing of feeders by means of earthing switches with short-circuit making capacity
Mechanical position indicators for the withdrawable part / switching-device truck and the feeder
earthing switch integrated in the mimic diagram at the panel front
Enclosure made of galvanized sheet steel
Front doors and lateral switchgear end walls are powder-coated with resistant epoxy resin material
Individual modular compartments in solid-wall design
Modular compartments bolted together
Further information to design features and design options is given in catalog HA 25.71.
110-0134.9 / 14
NXAIR / ≤ 40 kA