Racking The Contactor Truck To Service Position - Siemens NXAIR Operating Instructions Manual

Air-insulated switchgear ≤ 17.5 kv / ≤ 40 ka / ≤ 4000 a busbar current
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Operating the contactor panel with panel width 600 mm

14.7 Racking the contactor truck to service position

Preconditions
Contactor truck inserted in test position
Low-voltage connector plugged on
High-voltage door closed
Contactor in OPEN position
Feeder earthing switch in OPEN position
For electromagnetic interlock (optional):
Electromagnetic interlock deactivated
Racking crank for moving the contactor truck available
Double-bit key available
Padlock (optional) removed from operating slide
Fig. 266: Racking crank
Fig. 268: Position indicators on
high-voltage door
154
NOTICE
Maloperation
Racking the contactor truck to service position is only permissible if the contactor
is in OPEN position.
Switch the contactor to OPEN position, if required.
NXAIR / ≤ 40 kA
Fig. 267: Double-bit key with a diameter of 5 mm
Position indicator for contactor:
(1)
OPEN position
Position indicator for feeder earthing switch:
(2)
OPEN position
Position indicator for contactor truck:
(3)
test position
110-0134.9 / 14